EVERY TWO MONTHS
|
|
Fire Code
|
Duties
|
Item
|
Responsibility
|
|
6.5.5.7.(2)
|
Test
|
Sprinkler water flow devices for electrical supervision
|
Fire Protection Contractor
|
|
EVERY SIX MONTHS
|
|
2.6.1.13.
|
Inspect
|
Fire protection systems for commercial cooking equipment
|
Fire Protection Contractor
|
|
2.6.1.13.
|
Inspect
|
Hoods, grease removal devices, fan ducts and other appurtenances
|
Fire Protection Contractor
|
|
6.5.5.7.(3)
|
Test
|
Gate valve supervisory switches, and other supervisory devices
|
Fire Protection Contractor
|
|
6.7.1.1.(1)
|
Check
|
And clean crankcase breathers, governors and linkages on emergency generators
|
Fire Protection Contractor
|
|
6.8.1.1.(1)
|
Test
|
Special extinguishing systems
|
Fire Protection Contractor
|
|
ANNUALLY
|
|
2.2.3.7.
|
Inspect
|
Fire dampers and fire stop flaps (may be inspected on approved time schedule)
|
Mechanical Contractor
|
|
2.6.1.4.(1)
|
Inspect
|
All flues, and fluepipes
|
Mechanical Contractor
|
|
2.6.1.8.
|
Inspect
|
Disconnect switches for mechanical air conditioning and ventilation systems
|
Mechanical Contractor
|
|
2.6.1.13.
|
Test
|
Commercial cooking equipment fire protection systems; replace fusible links and sprinkler (other than glass-bulb type heads)
|
Fire Protection Contractor
|
|
2.7.3.3.(3)(b)
|
Test
|
Emergency lighting
|
Fire Protection Contractor
|
|
2.7.3.3.(4)
|
Test
|
Emergency lighting unit equipment for design duration
|
Fire Protection Contractor
|
|
6.2.7.1.
|
Inspect
|
All portable fire extinguishers
|
Fire Protection Contractor
|
|
6.3.2.2.
|
Test
|
Fire alarm system
|
Fire Protection Contractor
|
|
6.3.2.2.
|
Test
|
Automatic and manual operation of electromagnetic locks
|
Fire Protection Contractor
|
|
6.3.2.4.
|
Test
|
Voice communication system which is integrated with the fire alarm system
|
Fire Protection Contractor
|
|
Fire Code
|
Duties
|
Item
|
Responsibility
|
|
6.5.3.2.
|
Check
|
Exposed sprinkler system pipe hangers
|
Fire Protection Contractor
|
|
6.5.3.5.
|
Check
|
All sprinkler
|
Fire Protection Contractor
|
|
6.5.4.4.(2)
|
Inspect
|
For wear, rust or obstructions after removal of plug or caps on sprinkler Siamese connections
|
Fire Protection Contractor
|
|
6.5.5.3.
|
Test
|
Waterflow on wet sprinkler system using most hydraulically remote test connection
|
Fire Protection Contractor
|
|
6.5.5.5.
|
Test
|
Sprinkler system water supply pressure using main drain valve
|
Fire Protection Contractor
|
|
6.6.5.1.
|
Inspect
|
All fire hydrants
|
Fire Protection Contractor
|
|
6.6.5.2.(2)
|
Inspect
|
Hydrant port caps
|
Fire Protection Contractor
|
|
6.6.5.3.
|
Inspect
|
Fire hydrant barrel
|
Fire Protection Contractor
|
|
6.6.5.6.
|
Test
|
Fire hydrant water flow
|
Fire Protection Contractor
|
|
6.7.1.1.
|
Inspect and Service
|
Emergency generator and engine set. Operate generator at full load for two (2) hours
|
Fire Protection Contractor
|
|
6.7.1.3.
6.7.1.5.(1)
|
Inspect
|
Diesel generator. Drain and refill tank with fresh supply at least once a year
|
Fire Protection Contractor
|
|
6.8.1.1.(1)
|
Test
|
Special extinguishing systems
|
Fire Protection Contractor
|
|
EVERY TWO YEARS
|
|
6.7.1.1.
|
Inspect
|
And torque heads and valve adjustments for emergency generator engines
|
Fire Protection Contractor
|
|
EVERY THREE YEARS
|
|
6.7.1.1.
|
Inspect and Service
|
Injector nozzles and valve adjustments on diesel emergency power engines
|
Fire Protection Contractor
|
|
EVERY FIVE YEARS
|
|
6.2.7.1.
|
Test
|
H²0, CO² and dry chemical (dry chemical with stainless steel shell) extinguishers hydrostatically
|
Fire Protection Contractor
|
|
6.7.1.1.
|
Test
|
Insulation of emergency power generator windings
|
Fire Protection Contractor
|
|
Fire Code
|
Duties
|
Item
|
Responsibility
|
|
EVERY SIX YEARS
|
|
6.2.7.1.
|
Test
|
Empty stored pressure type extinguishers requiring 12 year hydrostatic test and subject to maintenance
|
Fire Protection Contractor
|
|
EVERY TWELVE YEARS
|
|
6.2.7.1.
|
Test
|
Hydrostatically, dry chemical (other than having stainless steel shell), dry powder, and vaporizing liquid type extinguishers
|
Fire Protection Contractor
|
|
EVERY FIFTEEN YEARS
|
|
6.5.4.2.
|
Inspect
|
Dry pipe sprinkler system for obstruction and flush where necessary
|
Fire Protection Contractor
|
|
ADDITIONAL REQUIREMENTS
( ONTARIO FIRE CODE)
|
|
2.2.3.5.
2.2.3.8.
|
Check
|
All doors in fire separations to ensure that they are closed
|
Building Maintenance
|
|
2.4.1.7.
|
Check
|
Lint traps in laundry equipment
|
Building Maintenance
|
|
2.6.1.13.
|
Clean
|
Hoods, grease removal devices, fans, ducts and other appurtenances shall be cleaned to bare metal at frequent intervals prior to surfaces becoming heavily contaminated with grease or oily sludge
|
Mechanical Contractor
|
|
2.7.1.7.(1)
|
Check and maintain
|
Corridors free of obstructions
|
Building Maintenance
|
|
6.2.7.1.
6.2.7.6.
|
Inspect and Recharge
|
Extinguishers after use or as indicated by an inspection or when performing maintenance
|
Fire Protection Contractor
|
|
6.3.3.2.(1)
|
Test
|
Smoke alarms maintained in operating condition according to the manufacturer's maintenance instructions
|
Fire Protection Contractor
|