PEMBROKE FIRE DEPARTMENT
273 Victoria Street
Pembroke , Ontario K8A 4K5
MAINTENANCE AND INSPECTION PROCEDURES FOR
FIRE PROTECTION SYSTEMS
The following list outlines the checks, inspections and tests required by the Ontario Fire Code (Ontario Regulation 388/97), as amended. A written record of the maintenance, tests and corrective measures will be kept in the building and will be available on request by the Chief Fire Official.
Written records shall be kept of all tests and corrective measures for a period of two years after they are made.
The information provided in this schedule is a guideline to the scope of work. The Fire Code should be consulted for exact details on the Codes listed in this section.
Check : means visual observation to ensure the device or system is in place and is not damaged or obstructed.
Inspect : means physical examination to determine that the device or system can be expected to perform in accordance with its intended operation or function.
Test : means operation of device or system to ensure that it will perform in accordance with its intended function.
Daily : every day of the week.
Weekly : a designated day of the week.
Monthly : a designated day of the month
Every 2 Months : during January, March, May, July, September and November
Every 3 Months : during February, May, August and November
Every 6 Months : during May and November
Annually : during May (along with two, three and six month dates, or as otherwise scheduled)
Note: Although designated to others, the ultimate responsibility for ensuring the Maintenance Procedures is fulfilled, belongs to the Building Owner.
Fire Code |
Duties |
Item |
Responsibility |
DAILY |
|||
2.5.1.2.(1) 2.5.1.3. |
Check |
to ensure streets, yards and private roadways provided for Fire Service access are kept clear
|
Building Maintenance |
2.7.3.1. 2.7.3.2. |
Check |
Exit lights |
Building Maintenance |
Fire Code |
Duties |
Item |
Responsibility
|
6.3.2.2. |
Check |
Fire alarm AC power and trouble light |
Building Maintenance
|
6.3.2.3. |
Check |
Central alarm and control facility |
Building Maintenance
|
WEEKLY
|
|||
2.6.1.3. |
Check |
Hoods, filters and ducts subject to accumulation of combustible deposits |
Building Maintenance |
2.6.1.13. |
Check |
Commercial cooking equipment |
Building Maintenance |
2.7.3.1 2.7.3.2 |
Check |
All exit lights equipped with dual bulbs are being maintained |
Building Maintenance |
6.5.3.1. |
Check |
That sprinkler system control valves are open and properly supervised |
Building Maintenance |
6.6.1.2. |
Inspect |
Valves for controlling fire protection water supply |
Building Maintenance |
MONTHLY
|
|||
2.2.3.4. |
Inspect |
All doors in fire separations |
Building Maintenance |
2.7.3.3.(1) |
Check |
Pilot lights on emergency lighting unit equipment |
Fire Protection Contractor |
2.7.3.3.(2) |
Check |
Inverter and emergency lighting unit equipment |
Fire Protection Contractor |
2.7.3.3.(3)(a) |
Test |
Inverter and all emergency lighting unit equipment for operation upon failure of primary power |
Fire Protection Contractor |
2.8.3.2.(1) |
Test |
Fire drill |
Fire Safety Committee and Staff |
6.2.7.2. |
Inspect |
All portable fire extinguishers |
Fire Protection Contractor |
6.3.2.2. |
Inspect |
Fire alarm batteries |
Fire Protection Contractor |
6.3.2.2. |
Test |
Fire alarm system |
Fire Protection Contractor |
6.3.2.4. |
Test |
Voice communication to and from floor area to the central alarm control |
Fire Protection Contractor |
6.5.5.2. |
Test |
The sprinkler system using the alarm test connection |
Fire Protection Contractor |
6.7.1.1. |
Test/Inspect |
Emergency generator set operated at 30 percent of rated load for 60 minutes |
Fire Protection Contractor |
EVERY TWO MONTHS
|
|||||
Fire Code |
Duties |
Item |
Responsibility |
||
6.5.5.7.(2) |
Test |
Sprinkler water flow devices for electrical supervision |
Fire Protection Contractor |
||
EVERY SIX MONTHS
|
|||||
2.6.1.13. |
Inspect |
Fire protection systems for commercial cooking equipment |
Fire Protection Contractor |
||
2.6.1.13. |
Inspect |
Hoods, grease removal devices, fan ducts and other appurtenances |
Fire Protection Contractor |
||
6.5.5.7.(3) |
Test |
Gate valve supervisory switches, and other supervisory devices |
Fire Protection Contractor |
||
6.7.1.1.(1) |
Check |
And clean crankcase breathers, governors and linkages on emergency generators |
Fire Protection Contractor |
||
6.8.1.1.(1) |
Test |
Special extinguishing systems |
Fire Protection Contractor |
||
ANNUALLY
|
|||||
2.2.3.7. |
Inspect |
Fire dampers and fire stop flaps (may be inspected on approved time schedule) |
Mechanical Contractor |
||
2.6.1.4.(1) |
Inspect |
All flues, and fluepipes |
Mechanical Contractor |
||
2.6.1.8. |
Inspect |
Disconnect switches for mechanical air conditioning and ventilation systems
|
Mechanical Contractor |
||
2.6.1.13. |
Test |
Commercial cooking equipment fire protection systems; replace fusible links and sprinkler (other than glass-bulb type heads) |
Fire Protection Contractor |
||
2.7.3.3.(3)(b) |
Test |
Emergency lighting |
Fire Protection Contractor |
||
2.7.3.3.(4) |
Test |
Emergency lighting unit equipment for design duration |
Fire Protection Contractor |
||
6.2.7.1. |
Inspect |
All portable fire extinguishers |
Fire Protection Contractor |
||
6.3.2.2. |
Test |
Fire alarm system |
Fire Protection Contractor |
||
6.3.2.2. |
Test |
Automatic and manual operation of electromagnetic locks |
Fire Protection Contractor |
||
6.3.2.4. |
Test |
Voice communication system which is integrated with the fire alarm system |
Fire Protection Contractor |
||
Fire Code |
Duties |
Item |
Responsibility
|
||
6.5.3.2. |
Check |
Exposed sprinkler system pipe hangers |
Fire Protection Contractor |
||
6.5.3.5. |
Check |
All sprinkler |
Fire Protection Contractor |
||
6.5.4.4.(2) |
Inspect |
For wear, rust or obstructions after removal of plug or caps on sprinkler Siamese connections |
Fire Protection Contractor |
||
6.5.5.3. |
Test |
Waterflow on wet sprinkler system using most hydraulically remote test connection |
Fire Protection Contractor |
||
6.5.5.5. |
Test |
Sprinkler system water supply pressure using main drain valve |
Fire Protection Contractor |
||
6.6.5.1. |
Inspect |
All fire hydrants |
Fire Protection Contractor |
||
6.6.5.2.(2) |
Inspect |
Hydrant port caps |
Fire Protection Contractor |
||
6.6.5.3. |
Inspect |
Fire hydrant barrel |
Fire Protection Contractor |
||
6.6.5.6. |
Test |
Fire hydrant water flow |
Fire Protection Contractor |
||
6.7.1.1. |
Inspect and Service |
Emergency generator and engine set. Operate generator at full load for two (2) hours |
Fire Protection Contractor |
||
6.7.1.3. 6.7.1.5.(1) |
Inspect |
Diesel generator. Drain and refill tank with fresh supply at least once a year |
Fire Protection Contractor |
||
6.8.1.1.(1) |
Test |
Special extinguishing systems |
Fire Protection Contractor |
||
EVERY TWO YEARS
|
|||||
6.7.1.1. |
Inspect |
And torque heads and valve adjustments for emergency generator engines |
Fire Protection Contractor |
||
EVERY THREE YEARS
|
|||||
6.7.1.1. |
Inspect and Service |
Injector nozzles and valve adjustments on diesel emergency power engines |
Fire Protection Contractor |
||
EVERY FIVE YEARS
|
|||||
6.2.7.1. |
Test |
H²0, CO² and dry chemical (dry chemical with stainless steel shell) extinguishers hydrostatically |
Fire Protection Contractor |
||
6.7.1.1. |
Test |
Insulation of emergency power generator windings |
Fire Protection Contractor |
||
Fire Code |
Duties |
Item |
Responsibility
|
||
EVERY SIX YEARS
|
|||||
6.2.7.1. |
Test |
Empty stored pressure type extinguishers requiring 12 year hydrostatic test and subject to maintenance |
Fire Protection Contractor |
||
EVERY TWELVE YEARS
|
|||||
6.2.7.1. |
Test |
Hydrostatically, dry chemical (other than having stainless steel shell), dry powder, and vaporizing liquid type extinguishers |
Fire Protection Contractor |
||
EVERY FIFTEEN YEARS
|
|||||
6.5.4.2. |
Inspect |
Dry pipe sprinkler system for obstruction and flush where necessary |
Fire Protection Contractor |
||
ADDITIONAL REQUIREMENTS ( ONTARIO FIRE CODE)
|
|||||
2.2.3.5. 2.2.3.8. |
Check |
All doors in fire separations to ensure that they are closed |
Building Maintenance |
||
2.4.1.7. |
Check |
Lint traps in laundry equipment |
Building Maintenance
|
||
2.6.1.13. |
Clean |
Hoods, grease removal devices, fans, ducts and other appurtenances shall be cleaned to bare metal at frequent intervals prior to surfaces becoming heavily contaminated with grease or oily sludge
|
Mechanical Contractor |
||
2.7.1.7.(1) |
Check and maintain |
Corridors free of obstructions |
Building Maintenance |
||
6.2.7.1. 6.2.7.6.
|
Inspect and Recharge |
Extinguishers after use or as indicated by an inspection or when performing maintenance |
Fire Protection Contractor |
||
6.3.3.2.(1) |
Test |
Smoke alarms maintained in operating condition according to the manufacturer's maintenance instructions |
Fire Protection Contractor |
||